Purpose of the gateway

X2BACnet converts other device protocols to standard BACnet. The source mentions BACnet MS/TP and BACnet/IP; use the complete model’s specifications to confirm actual interfaces, forwarding functions and communication roles.

Distinguish the capacities

BACnet object counts and a hardware gateway’s total acquisition-point capacity are different parameters. The source specifies 1,024 objects of each of nine types for the version it describes. Do not add these figures together and apply that total to every hardware model.

BACnet objectAccess in the sourceObjects per type in the source
AIRead only1024
AORead/write1024
AVRead/write1024
BIRead only1024
BORead/write1024
BVRead/write1024
MSIRead only1024
MSORead/write1024
MSVRead/write1024

Checks before selection

Confirm the project requirements individually.

  1. Record the complete model, hardware revision and firmware version.
  2. Check that model’s data-point capacity and BACnet object counts.
  3. Confirm the required BACnet/IP, BACnet MS/TP or other interface, communication direction, roles and physical ports.

Verification

Test conversion with a few points of known types. At the reading system, check object types, identifiers, values and applicable access permissions. An object-count figure does not replace the complete model’s capacity specification.