Edited English translation of the original Chinese case. The original images and on-screen Chinese text are retained. Model names and example settings describe that source version; check current model documents for a new project.

Project scope and equipment

The source describes an unnamed chiller-plant project, shown as “XX project,” rather than identifying a customer or publishing acceptance results. Its plant includes chillers, chilled-water and cooling-water pumps, cooling towers, valves and field sensors.

  • HMI2004-A9 web HMI gateway: the network-level control engine, collecting points and providing the browser interface.
  • BAC1002-ARM gateway: collects third-party equipment data and presents it in the protocol used by the HMI.
  • DDC2001-8642 and IOM modules: the controller names recorded in this historical project, handling field inputs, calculations and outputs.

HMI2004-A9 in the original source

HMI2004-A9 in the original source

BAC1002-ARM in the original source

BAC1002-ARM in the original source

DDC controller in the original source

DDC controller in the original source

Data connection

Temperature and pressure sensors, pump and tower status contacts, and valve commands and feedback are connected through the DDC and IOM modules. The source connects IOM to the DDC over BACnet MS/TP, then enables BACnet/IP forwarding from the DDC to the network.

Original DDC and IOM assembly

Original DDC and IOM assembly

Third-party equipment with Modbus RTU interfaces, such as chillers or water-treatment equipment, is connected through the BAC gateway. The documented network path uses BACnet/IP. The source also mentions Modbus TCP as an alternative; that is a separate configuration, not a second connection automatically present in this project.

The HMI gateway reads the DDC and gateway points over BACnet/IP and combines them with the project logic and graphics.

Configuration workflow

  1. Configure acquisition points in X2View from the equipment point lists.
  2. Write the project logic using JavaScript or the graphical programming interface.
  3. Use offline simulation to check and adjust the logic.
  4. Create the HMI graphics, bind their points, and upload the completed project to the HMI gateway.
  5. Open the gateway address in a browser to use the configured interface.

Point acquisition in X2View

Point acquisition in X2View

Original JavaScript programming screen

Original JavaScript programming screen

Original JavaScript example

Original JavaScript example

Original graphical programming screen

Original graphical programming screen

Original HMI editing screen

Original HMI editing screen

Operating the documented plant

Browser access and overview

The source opens a browser using the desktop icon Browser icon and enters the HMI engine IP address. The overview shows three centrifugal chillers; the upper-right selector changes between the north and south plant displays.

Original plant overview

Original plant overview

The source illustrates the chiller Chiller symbol, chilled-water pump Chilled-water pump symbol, cooling tower Cooling tower symbol and cooling-water pump Cooling-water pump symbol. Chilled-water and cooling-water bypass valves are shown as Chilled-water bypass valve and Cooling-water bypass valve.

The on/off-valve graphic On/off valve display separates the command from feedback: the control bar shows the ON/OFF command, while the center indicator is green for fully open and red for fully closed.

Automatic, manual and one-touch modes

The mode selector Mode selector switches between the three project modes. In automatic mode, the source's chiller control Automatic-mode chiller control coordinates the associated valves, pumps and tower.

The documented start sequence opens the chilled-water and cooling-water valves, starts the pumps and tower after the valves open, waits five minutes, then starts the chiller. Its shutdown sequence stops the chiller, stops cooling-water pumps and towers after five minutes, allows the chilled-water pump to circulate for 20 minutes, then closes the valves after a further documented delay of 30 minutes. These are the original project's settings, not general plant design values.

The source initially runs three tower fans and the corresponding valves. After a delay, its staging logic adds fans above 32°C cooling-water return temperature and removes fans below 27°C. The south plant has a different sequence: the cooling-water pump starts before the associated valve, followed by a delay and valve opening. That exception belongs to the original site's logic and must not be transferred to other equipment without reviewing its operating requirements.

In manual mode, pumps, chillers and valves are operated individually, either from the interface or at the equipment. The one-touch controls One-touch start and stop controls apply only in one-touch mode. The source starts an available non-faulted chiller with the shortest recorded operating time, then uses chiller current percentage to determine staging. It describes two duty chillers and one standby chiller, with fault status and runtime influencing selection. One-touch shutdown stops chillers first and then stops the related pumps, towers and valves with delays.

The seasonal selector Seasonal selector changes the project between cooling and heating. In the original program, the cooling sequence runs in summer mode; seasonal valves select the associated heating or cooling path.

Pumps, towers and individual equipment pages

The plant has four chilled-water pumps, shown by Chilled-water pump overview. The source distinguishes remote mode Remote-mode indication from local mode Local-mode indication and shows a no-fault indication No-fault indication. The HMI controls the pumps only when they are in remote mode.

It also describes four cooling-water pumps Cooling-water pump overview, with their own remote Remote indication, local Local indication and fault-status No-fault indication displays.

Original pump detail page

Original pump detail page

The pump detail page includes runtime and variable-frequency controls. The frequency button Frequency entry control accepts the project setpoint; the source imposes a 30 Hz lower limit while the pump is running. Its local override controls Mode before override and Forced-mode indication allow individual pump operation without changing the outer system mode. This is a description of that project interface, not a commissioning instruction for an unspecified pump.

Original pump frequency or control detail

Original pump frequency or control detail

Original cooling-tower detail page

Original cooling-tower detail page

The tower page uses a similar override workflow, illustrated by Tower mode selector, Tower forced mode and Tower command. The source also calls for opening the associated valve on the overview Associated valve control.

Original chiller symbol or control display

Original chiller symbol or control display

Original chiller detail page

Original chiller detail page

The chiller detail page exposes the recorded parameters and a separate manual-start control Manual chiller-start control. The original text cautions that manual operation requires the associated valves, pumps and towers to be managed individually.

Weekly schedules and holidays

Original schedule page

Original schedule page

The timer opens separate north-plant and south-plant one-touch schedules. Select a day, add a time entry Schedule entry, and set its command: 1 for start and 0 for stop. Enable the entry Enable schedule entry and confirm it; the configured day is marked Configured-day indication.

Original holiday calendar

Original holiday calendar

The holiday calendar marks dates on which the ordinary weekly commands are not executed.

Version and project limits

Model names, display controls, interlocks, temperatures, frequency limits and delays above are taken from this historical example. Confirm the exact current model, hardware/firmware revision, point list and site program for a new project. The source does not provide measured energy savings, quantitative reliability results or an independent acceptance report.