Requirement
The Tianjin Huibinyuan project needed shared monitoring and operating-mode control for Haier VRV air-conditioning systems in two buildings. The intended supervisory platform was Niagara AX3.8.
Solution
The source uses three HMI2004-Lite gateways for 14 equipment groups. Acquisition was configured from the manufacturer’s Modbus RTU point list, and the BACnet/IP server was enabled for supervisory integration.
Completed work and the remaining boundary
The article records field-communication commissioning and local HMI screens for initial user operation. The BA-system connection was still pending because of the site network. A configured BACnet interface must therefore not be described as completed Niagara integration.