Product overview
1 Ethernet port and 2 RS485 serial ports. Adds MBus and DLT645 acquisition to the Lite baseline for water, heat, energy and electricity meters.
Key functions
COV and cross-subnet access
Supports COV subscriptions and BBMD cross-subnet access for change notifications and BACnet network integration.
BACnet alarms and events
Provides BACnet alarm and event functions for monitoring objects configured from the field point list.
Data-format processing
Supports linear scaling, bit extraction and byte-order conversion to handle different device data formats.
Scripts and triggers
Use JS scripts and triggers for required control logic alongside the configured communication points.
Web monitoring and operation
Use built-in web pages to view, configure and monitor device data during commissioning and operation.
Point-list configuration
Configure acquisition and forwarding mappings from the field point list, then upload the project for supervisory-system access.
Typical applications
Lighting-device connectivity and management; Field-meter data integration.
Model selection essentials
- This model has multiple hardware editions; confirm the processor, supply and port configuration when ordering.
Model designation and meter acquisition
Model designation: 1 Ethernet port and 2 serial ports. The manufacturer confirms meter-oriented acquisition with MBus and DLT645 added to the Lite baseline. The listed acquisition protocols are explicitly documented in both catalog editions; the Lite baseline does not imply every meter driver. Check the matching datasheet for forwarding capabilities and power requirements.
Both serial ports are RS485 (COM1 and COM2). The documented MBus acquisition is for four-wire MBus devices. Do not connect two-wire MBus devices directly to these RS485 ports.
Current product specifications
This model has multiple documented hardware versions. Choose the matching version below; a single specification set has not been assumed.
BAC1002-MBus — MBus to BACnet gateway (standard power edition) · Chinese PDF
Current product specifications
Specifications are sourced from the supplied 2026 product catalog. Unspecified values remain unconfirmed.
| Parameter | Specification |
|---|---|
| Total serial ports | 2 |
| RS485 ports | 2 |
| Ethernet ports | 1 |
| Point capacity | 512 |
| Acquisition protocols | MBus_WaterMeter / MBus_EnergyMeter_EN / MBus_EnergyMeter / Modbus RTU / Modbus TCP / DLT645-1997/2007 / Simulator |
| Forwarding protocols | OPC UA / BACnet/IP |
| Physical interfaces | Ethernet / RS485 |
Model datasheets
- File unavailable in this language
BAC1002-MBus — MBus to BACnet gateway (DC 24 V edition) · Chinese PDF
Current product specifications
Specifications are sourced from the supplied 2026 product catalog. Unspecified values remain unconfirmed.
| Parameter | Specification |
|---|---|
| Total serial ports | 2 |
| RS485 ports | 2 |
| Ethernet ports | 1 |
| Point capacity | 512 |
| Acquisition protocols | MBus_WaterMeter / MBus_EnergyMeter_EN / MBus_EnergyMeter / Modbus RTU / Modbus TCP / DLT645-1997/2007 / Simulator |
| Forwarding protocols | OPC UA / BACnet/IP / BACnet MS/TP |
| Physical interfaces | Ethernet / RS485 |
Model datasheets
- File unavailable in this language