Product overview

Organizes field-device data into browser-based HMI screens for building or industrial monitoring and provides interfaces for other supervisory systems.

Selection and reading guide

  • Acquisition covers more than 500 protocols; check the driver against each connected device. This edition also supports OPC DA acquisition.
  • Check the acquisition direction against: OPC DA. Similar names do not imply the same client/server role or serial transport.
  • For supervisory integration, first check the forwarding interfaces—BACnet, Modbus, MQTT, OPC UA—then check this model’s communication roles and configuration steps.
  • Check the field point list against the communication capacity of 2048 points and 128 devices; count physical terminals separately from communication points.

Model document guide

  • File unavailable in this language; purpose and functions: page 3; specification references: pages 2, 4

Current product specifications

Specifications are sourced from the supplied 2026 product catalog. Unspecified values remain unconfirmed.

ParameterSpecification
Total serial ports4
RS485 ports4
Ethernet ports2
Point capacity2048
Device capacity128
Acquisition protocolsOPC DA
Forwarding protocolsBACnet / Modbus / MQTT / OPC UA
Physical interfacesRS485 / Ethernet
HMI visualizationSupported

Model notes: More than 500 protocols. OPC DA acquisition is supported.